A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted series of network requests can lead to a denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.An attacker can trigger this denial-of-service condition by sending a single Modbus TCP message to port 503 using the Write Single Register function code (6) to write the value 1 to register 4352. This action changes the Modbus address to 15. After this message is sent, the device will be in a denial-of-service state.
| Métrique | Valeur | Interprétation |
|---|---|---|
|
AV (Vecteur d'Attaque)
Attack Vector
|
Network (N)
|
Exploit possible à distance via réseau (HTTP, API, etc.) |
|
AC (Complexité d'Attaque)
Attack Complexity
|
Low (L)
|
Peu de conditions requises pour exploiter |
|
PR (Privilèges Requis)
Privileges Required
|
None (N)
|
Aucune authentification requise |
|
UI (Interaction Utilisateur)
User Interaction
|
None (N)
|
Aucune interaction utilisateur nécessaire |
|
S (Périmètre)
Scope
|
Unchanged (U)
|
Impact reste dans le périmètre du composant compromis |
|
C (Impact Confidentialité)
Confidentiality Impact
|
None (N)
|
Aucune divulgation d'informations |
|
I (Impact Intégrité)
Integrity Impact
|
None (N)
|
Aucune modification de données possible |
|
A (Impact Disponibilité)
Availability Impact
|
High (H)
|
Interruption totale du service possible |