The Honeywell Experion PKS contains an Integer Underflow vulnerability in the component Control Data Access (CDA). An attacker could potentially exploit this vulnerability, leading to Input Data Manipulation, which could result in improper integer data value checking during subtraction leading to a denial of service. Honeywell recommends updating to the most recent version of Honeywell Experion PKS:520.2 TCU9 HF1 and 530.1 TCU3 HF1. The affected Experion PKS products are C300 PCNT02, C300 PCNT05, FIM4, FIM8, UOC, CN100, HCA, C300PM, and C200E. The Experion PKS versions affected are from 520.1 through 520.2 TCU9 and from 530 through 530 TCU3.
| Métrique | Valeur | Interprétation |
|---|---|---|
|
AV (Vecteur d'Attaque)
Attack Vector
|
Network (N)
|
Exploit possible à distance via réseau (HTTP, API, etc.) |
|
AC (Complexité d'Attaque)
Attack Complexity
|
Low (L)
|
Peu de conditions requises pour exploiter |
|
PR (Privilèges Requis)
Privileges Required
|
None (N)
|
Aucune authentification requise |
|
UI (Interaction Utilisateur)
User Interaction
|
None (N)
|
Aucune interaction utilisateur nécessaire |
|
S (Périmètre)
Scope
|
Unchanged (U)
|
Impact reste dans le périmètre du composant compromis |
|
C (Impact Confidentialité)
Confidentiality Impact
|
None (N)
|
Aucune divulgation d'informations |
|
I (Impact Intégrité)
Integrity Impact
|
Low (L)
|
Modification limitée des données possible |
|
A (Impact Disponibilité)
Availability Impact
|
High (H)
|
Interruption totale du service possible |