> CVE-2022-31206 [CRITICAL]

« BACK_TO_HOME
PUBLISHED
2022-07-26 22:15
MODIFIED
2024-11-21 07:04
CVSS_SCORE V3
9.8
EPSS (Prob. Exploit)
1.12%
Top 33.4%
DATA SOURCES:
NVD 🔗 2025-10-18 CVE PROJECT 🔗 2026-01-19 FIRST EPSS 🔗 2026-11-15

> DESCRIPTION

The Omron SYSMAC Nx product family PLCs (NJ series, NY series, NX series, and PMAC series) through 2022-005-18 lack cryptographic authentication. These PLCs are programmed using the SYMAC Studio engineering software (which compiles IEC 61131-3 conformant POU code to native machine code for execution by the PLC's runtime). The resulting machine code is executed by a runtime, typically controlled by a real-time operating system. The logic that is downloaded to the PLC does not seem to be cryptographically authenticated, allowing an attacker to manipulate transmitted object code to the PLC and execute arbitrary machine code on the processor of the PLC's CPU module in the context of the runtime. In the case of at least the NJ series, an RTOS and hardware combination is used that would potentially allow for memory protection and privilege separation and thus limit the impact of code execution. However, it was not confirmed whether these sufficiently segment the runtime from the rest of the RTOS.

> AFFECTED_PRODUCTS

Omron - Nx701 1600 Firmware
< 1.29
Omron - Nx701 1700 Firmware
< 1.29
Omron - Nx701 Z700 Firmware
< 1.29
Omron - Nx701 Z600 Firmware
< 1.29
Omron - Nx701 1720 Firmware
< 1.29
Omron - Nx701 1620 Firmware
< 1.29
Omron - Nj501 1500 Firmware
< 1.49
Omron - Nj501 1300 Firmware
< 1.49
Omron - Nj501 5300 Firmware
< 1.49
Omron - Nj501 1520 Firmware
< 1.49
Omron - Nj501 1420 Firmware
< 1.49
Omron - Nj501 1320 Firmware
< 1.49
Omron - Nj101 1020 Firmware
< 1.49
Omron - Nj101 9020 Firmware
< 1.49
Omron - Nj501 1340 Firmware
< 1.49
Omron - Nj501 4500 Firmware
< 1.49
Omron - Nj501 4400 Firmware
< 1.49
Omron - Nj501 4300 Firmware
< 1.49
Omron - Nj501 4320 Firmware
< 1.49
Omron - Nj301 1200 Firmware
< 1.49
Omron - Nj301 1100 Firmware
< 1.49
Omron - Nj101 1000 Firmware
< 1.49
Omron - Nj101 9000 Firmware
< 1.49
Omron - Nj501 1400 Firmware
< 1.49
Omron - Nj501 5300 1 Firmware
< 1.49

> CVSS V3 METRICS

CVSS_VECTOR
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

> MÉTRIQUES CVSS DÉTAILLÉES

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Métrique Valeur Interprétation
AV (Vecteur d'Attaque)
Attack Vector
Network (N)
Exploit possible à distance via réseau (HTTP, API, etc.)
AC (Complexité d'Attaque)
Attack Complexity
Low (L)
Peu de conditions requises pour exploiter
PR (Privilèges Requis)
Privileges Required
None (N)
Aucune authentification requise
UI (Interaction Utilisateur)
User Interaction
None (N)
Aucune interaction utilisateur nécessaire
S (Périmètre)
Scope
Unchanged (U)
Impact reste dans le périmètre du composant compromis
C (Impact Confidentialité)
Confidentiality Impact
High (H)
Divulgation totale d'informations
I (Impact Intégrité)
Integrity Impact
High (H)
Modification totale des données possible
A (Impact Disponibilité)
Availability Impact
High (H)
Interruption totale du service possible

> RÉSUMÉ DES IMPACTS

Confidentialité
High
Divulgation totale d'informations
Intégrité
High
Modification totale des données possible
Disponibilité
High
Interruption totale du service possible

> HISTORIQUE DES MODIFICATIONS

Première apparition
26/07/2022 22:15
Source: NVD
📊 ENRICHISSEMENT 18/10/2025 14:34
CVEPROJECT
Champ modifié: CVE Project
Ancienne valeur:
Non
Nouvelle valeur:
Oui
Total des modifications: 1 Dernière mise à jour: 1 year ago
« BACK_TO_HOME