> CVE-2022-30315 [CRITICAL]

« BACK_TO_HOME
PUBLISHED
2022-07-28 16:15
MODIFIED
2024-11-21 07:02
CVSS_SCORE V3
9.8
EPSS (Prob. Exploit)
0.99%
Top 37.3%
DATA SOURCES:
NVD đź”— 2025-10-18 CVE PROJECT đź”— 2026-01-19 FIRST EPSS đź”— 2026-11-08

> DESCRIPTION

Honeywell Experion PKS Safety Manager (SM and FSC) through 2022-05-06 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0053, there is a Honeywell Experion PKS Safety Manager insufficient logic security controls issue. The affected components are characterized as: Honeywell FSC runtime (FSC-CPU, QPP), Honeywell Safety Builder. The potential impact is: Remote Code Execution, Denial of Service. The Honeywell Experion PKS Safety Manager family of safety controllers utilize the unauthenticated Safety Builder protocol (FSCT-2022-0051) for engineering purposes, including downloading projects and control logic to the controller. Control logic is downloaded to the controller on a block-by-block basis. The logic that is downloaded consists of FLD code compiled to native machine code for the CPU module (which applies to both the Safety Manager and FSC families). Since this logic does not seem to be cryptographically authenticated, it allows an attacker capable of triggering a logic download to execute arbitrary machine code on the controller's CPU module in the context of the runtime. While the researchers could not verify this in detail, the researchers believe that the microprocessor underpinning the FSC and Safety Manager CPU modules is incapable of offering memory protection or privilege separation capabilities which would give an attacker full control of the CPU module. There is no authentication on control logic downloaded to the controller. Memory protection and privilege separation capabilities for the runtime are possibly lacking. The researchers confirmed the issues in question on Safety Manager R145.1 and R152.2 but suspect the issue affects all FSC and SM controllers and associated Safety Builder versions regardless of software or firmware revision. An attacker who can communicate with a Safety Manager controller via the Safety Builder protocol can execute arbitrary code without restrictions on the CPU module, allowing for covert manipulation of control operations and implanting capabilities similar to the TRITON malware (MITRE ATT&CK software ID S1009). A mitigating factor with regards to some, but not all, of the above functionality is that these require the Safety Manager physical keyswitch to be in the right position.

> AFFECTED_PRODUCTS

ℹ️ Aucun produit affecté n'a encore été publié par NVD pour cette CVE.

> CVSS V3 METRICS

CVSS_VECTOR
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

> MÉTRIQUES CVSS DÉTAILLÉES

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Métrique Valeur Interprétation
AV (Vecteur d'Attaque)
Attack Vector
Network (N)
Exploit possible à distance via réseau (HTTP, API, etc.)
AC (Complexité d'Attaque)
Attack Complexity
Low (L)
Peu de conditions requises pour exploiter
PR (Privilèges Requis)
Privileges Required
None (N)
Aucune authentification requise
UI (Interaction Utilisateur)
User Interaction
None (N)
Aucune interaction utilisateur nécessaire
S (Périmètre)
Scope
Unchanged (U)
Impact reste dans le périmètre du composant compromis
C (Impact Confidentialité)
Confidentiality Impact
High (H)
Divulgation totale d'informations
I (Impact Intégrité)
Integrity Impact
High (H)
Modification totale des données possible
A (Impact Disponibilité)
Availability Impact
High (H)
Interruption totale du service possible

> RÉSUMÉ DES IMPACTS

Confidentialité
High
Divulgation totale d'informations
Intégrité
High
Modification totale des données possible
Disponibilité
High
Interruption totale du service possible

> HISTORIQUE DES MODIFICATIONS

Première apparition
28/07/2022 16:15
Source: NVD
📊 ENRICHISSEMENT 18/10/2025 14:34
CVEPROJECT
Champ modifié: CVE Project
Ancienne valeur:
Non
Nouvelle valeur:
Oui
Total des modifications: 1 Dernière mise à jour: 1 year ago
« BACK_TO_HOME