Honeywell Experion PKS Safety Manager 5.02 uses Hard-coded Credentials. According to FSCT-2022-0052, there is a Honeywell Experion PKS Safety Manager hardcoded credentials issue. The affected components are characterized as: POLO bootloader. The potential impact is: Manipulate firmware. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 serial interface for firmware management purposes. When booting, the Safety Manager exposes the Enea POLO bootloader via this interface. Access to the boot configuration is controlled by means of credentials hardcoded in the Safety Manager firmware. The credentials for the bootloader are hardcoded in the firmware. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize these credentials to control the boot process and manipulate the unauthenticated firmware image (see FSCT-2022-0054).
| Métrique | Valeur | Interprétation |
|---|---|---|
|
AV (Vecteur d'Attaque)
Attack Vector
|
Physical (P)
|
Exploit nécessite un accès physique à l'appareil |
|
AC (Complexité d'Attaque)
Attack Complexity
|
Low (L)
|
Peu de conditions requises pour exploiter |
|
PR (Privilèges Requis)
Privileges Required
|
None (N)
|
Aucune authentification requise |
|
UI (Interaction Utilisateur)
User Interaction
|
None (N)
|
Aucune interaction utilisateur nécessaire |
|
S (Périmètre)
Scope
|
Unchanged (U)
|
Impact reste dans le périmètre du composant compromis |
|
C (Impact Confidentialité)
Confidentiality Impact
|
None (N)
|
Aucune divulgation d'informations |
|
I (Impact Intégrité)
Integrity Impact
|
High (H)
|
Modification totale des données possible |
|
A (Impact Disponibilité)
Availability Impact
|
None (N)
|
Aucune interruption de service |