Bently Nevada condition monitoring equipment through 2022-04-29 mishandles authentication. It utilizes the TDI command and data protocols (60005/TCP, 60007/TCP) for communications between the monitoring controller and System 1 and/or Bently Nevada Monitor Configuration (BNMC) software. These protocols provide configuration management and historical data related functionality. Neither protocol has any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a subset of) desired functionality.
| Métrique | Valeur | Interprétation |
|---|---|---|
|
AV (Vecteur d'Attaque)
Attack Vector
|
Network (N)
|
Exploit possible à distance via réseau (HTTP, API, etc.) |
|
AC (Complexité d'Attaque)
Attack Complexity
|
Low (L)
|
Peu de conditions requises pour exploiter |
|
PR (Privilèges Requis)
Privileges Required
|
None (N)
|
Aucune authentification requise |
|
UI (Interaction Utilisateur)
User Interaction
|
None (N)
|
Aucune interaction utilisateur nécessaire |
|
S (Périmètre)
Scope
|
Unchanged (U)
|
Impact reste dans le périmètre du composant compromis |
|
C (Impact Confidentialité)
Confidentiality Impact
|
None (N)
|
Aucune divulgation d'informations |
|
I (Impact Intégrité)
Integrity Impact
|
High (H)
|
Modification totale des données possible |
|
A (Impact Disponibilité)
Availability Impact
|
High (H)
|
Interruption totale du service possible |