A vulnerability has been identified in Climatix POL908 (BACnet/IP module) (All versions), Climatix POL909 (AWM module) (All versions < V11.32). A persistent cross-site scripting (XSS) vulnerability exists in the web server access log page of the affected devices that could allow an attacker to inject arbitrary JavaScript code via specially crafted GET requests. The code could be potentially executed later by another (privileged) user. The security vulnerability could be exploited by an attacker with network access to the affected system. Successful exploitation requires no system privileges. An attacker could use the vulnerability to compromise the confidentiality and integrity of other users' web sessions.
| Métrique | Valeur | Interprétation |
|---|---|---|
|
AV (Vecteur d'Attaque)
Attack Vector
|
Network (N)
|
Exploit possible à distance via réseau (HTTP, API, etc.) |
|
AC (Complexité d'Attaque)
Attack Complexity
|
Low (L)
|
Peu de conditions requises pour exploiter |
|
PR (Privilèges Requis)
Privileges Required
|
None (N)
|
Aucune authentification requise |
|
UI (Interaction Utilisateur)
User Interaction
|
Required (R)
|
Nécessite une action utilisateur (clic lien, ouverture fichier, etc.) |
|
S (Périmètre)
Scope
|
Changed (C)
|
Impact s'étend au-delà du composant compromis |
|
C (Impact Confidentialité)
Confidentiality Impact
|
Low (L)
|
Divulgation limitée d'informations |
|
I (Impact Intégrité)
Integrity Impact
|
Low (L)
|
Modification limitée des données possible |
|
A (Impact Disponibilité)
Availability Impact
|
None (N)
|
Aucune interruption de service |